03-02-21 West Building Resources Flipbook

West Building

Hall WA1-WA4 | 6,120 each hall

Hall WF1 | 1,462

Hall WB1 and WB4 | 6,120 each hall

Hall WF2 | 2,100

Hall WB2 and WB3 | 3,060 each hall

Hall WF3 | 468

Hall WC | 7,120

Hall WF4 | 1,152

Hall WD1 | 3,630

Valencia A (Room W415A) | 1,953

Hall WD2 | 7,711

Valencia B (Room W415B) | 918

Hall WE1 | 4,968

Valencia C (Room W415C) | 918

Hall WE2 | 4,484

Valencia D (Room W415D) | ,953

• Chair size – 20”w x 21”d

• No more than 14 chairs in a row without a break

• No more than 24 rows in a section without a break

• Distance between rows should be a minimum of 14” back to front, prefer at least 16” or more

• Aisle widths must be at least 8’ wide (Pending Fire Marshal approval)

• First row of chairs must be at least 8’ from the stage

• Structures/seating must be at least 20’ off the entrance and exit doors

• If stage is set on the Dock side of the Exhibit Hall, an Emergency Exit must be provided on each end of the stage. The Emergency Exit must also be identified with lighted Exit signs with battery back-up. Clear dedicated exiting paths must be created and maintained backstage throughout the event.

• Baffling is not permitted

• Fire cabinets and Fire strobes cannot be blocked

• Removal of Bulk Trash is the responsibility of the General Service Contractor/Production Company

• Event Security is required during move-in, show and move-out

• When submitting Floor Plans for Fire Marshal Approval, the electrical ports (floor pocket grid) should be shown as a point of reference

• Fire Marshal approval

Page 43